Uredljive vzorčne vrednostiVaša ocena
Posodobljen rezultatNeprekinjeno · Moč
5 kW
Moč · kVA
5.56 kVA
Vrh · Moč
6.5 kW
Najmanj 3 s
Rezultati so namenjeni načrtovanju. Pred izbiro opreme preverite predpostavke.
Lokacija in tarife se ne pridobijo samodejno. Izračun uporablja vnesene vrednosti.
Kako uporabljati kalkulator
Vnesite sočasno obremenitev in zagonski vrh. V podatkih razsmernika preverite tako kW kot kVA.
Metoda izračuna
Continuous kW = load × (1 + headroom) ÷ 1,000. kVA = continuous kW ÷ power factor. Required peak rating = greater of total startup load and continuous requirement.
Pred uporabo rezultata
Choose an inverter that meets BOTH its continuous kW and kVA ratings, and the peak rating for the specified duration. PV input voltage/current limits, phase, battery discharge capability and charging power require separate checks.
Is a 5 kVA inverter always 5 kW?
No. Its rated output power factor and manufacturer specifications determine its usable continuous watts.