输入参数
可编辑的示例值估算结果
实时计算结果最小 · 温度 · Voc
214.63 V
最大 · 温度 · Vmp
140.87 V
最小 · 温度 · Vmp
184.76 V
Limit checks failed
0
这些结果用于初步规划。选购设备前,请核对计算假设。
系统不会自动获取位置或电价,计算以您输入的数据为准。
如何使用这个计算器
一次检查一个MPPT输入。填写板参数、温度和逆变器限制,查看有没有超过电压或电流边界。
计算方法
Temperature-corrected voltage = series × reference voltage × [1 + coefficient / 100 × (cell temperature − 25)]. Compare cold Voc with absolute PV maximum; hot and cold Vmp with MPPT window. Compare parallel Imp and Isc with their separate current limits.
使用结果之前
Passing these selected checks is not full equipment approval. Verify startup voltage, permitted array wattage, irradiance/current correction factors, connector limits and manufacturer string-design rules. Inputs describe ONE MPPT, not combined independent MPPT channels.
What should I check before using this estimate?
Passing these selected checks is not full equipment approval. Verify startup voltage, permitted array wattage, irradiance/current correction factors, connector limits and manufacturer string-design rules. Inputs describe ONE MPPT, not combined independent MPPT channels.