Ємність акумуляторного банку

Size nominal storage for your backup load, duration and usable battery depth.

Ваші дані

Редаговані приклади

Ваша оцінка

Live calculation
Номінально · Ємність
5.56 kWh
Ємність
115.74 Ah
At 48 V
AC · Енергія
4 kWh
Planning estimates, not equipment approval. Review the assumptions below before choosing a system.

No location or tariff is detected automatically. All results use the values you enter.

This guide is available in English and Urdu. English is shown below.

What is this tool used for?

Use this calculator when you know which appliances need backup and how long they must run, but do not yet know the battery capacity to buy.

How to use this calculator

Enter the average backup load, backup hours, nominal battery-bank voltage, usable depth of discharge and battery-to-AC efficiency. Use the manufacturer's permitted usable capacity rather than assuming the whole battery is available.

Understanding your results

Nominal kWh is the required stored energy rating before usability and conversion losses. Ah is the capacity at your selected bank voltage, so compare Ah figures only at the same voltage. Aging and temperature need additional allowance.

Метод розрахунку

Nominal kWh = load watts × hours ÷ (1,000 × DoD × efficiency). Bank Ah = nominal kWh × 1,000 ÷ nominal bank voltage. Enter 24 hours for one day of continuous backup.

Методологія →

Перед використанням результату

Ah is capacity at the stated bank voltage, not the sum of series-connected battery Ah ratings. Allow separately for age, temperature, peak discharge and recharge time.

Do batteries in series add amp-hours?

No. Series connections add voltage while Ah stays the same; parallel strings add Ah at the same voltage.